# Heat exchanger: Working

Source page: https://www.materialinsights.org/products/p_heat_exchanger/prod-working/

#### What it is

The product and the job it does, in a short paragraph

A plate heat exchanger passes heat from one liquid to another through thin metal plates, keeping the two liquids apart. The functional unit is one plate heat exchanger of 1 MW duty. The scope is heat-exchange units of HS 8419.50 built from stacked plates, gasketed or brazed. Shell and tube, air-cooled and welded block units, economisers and recuperators are left out. Masses here are scaled from maker units of 0.5 to about 1.2 MW ^[5]^[4]^[31]^[32].

as of 2026-11-17

#### How it works

How it does its job, step by step in plain words

A pack of corrugated plates is stacked so that the hot and cold liquids run in alternate channels ^[1]. The corrugations create strong turbulence over the whole plate, which raises heat transfer and reduces fouling ^[6]. Heat crosses each plate by conduction. Counter-current flow gives the most efficient performance, and close temperature approaches are possible ^[7]^[6]. In a gasketed unit, rubber gaskets seal the channels and the pack is held in a frame. In a brazed unit the plates are joined with copper in a vacuum oven, so there are no gaskets ^[29]. External pumps push the liquids through. A higher pressure drop needs fewer plates and costs less to buy, but costs more to pump ^[8].

as of 2026-11-17

#### Key specifications

The numbers that describe it, each with unit, variant, year and source

| Spec | Value | Unit | Variant | Source |
|---|---|---|---|---|
| Mass of a 1 MW unit, gasketed (calculated by scaling linearly with duty: Alfa Laval T5-BFG-75M, 100.9 kg at 500 kW, gives 201.8 kg; Alfa Laval T8-BFG-63M, 266 kg at 1,000 Mcal/h or about 1,163 kW, gives 228.7 kg) | 201.8 | kg | Gasketed | ^[5]^[31] |
| Mass of a 1 MW unit, brazed (calculated by scaling linearly with duty: ACV 900 kW unit, 75.8 kg empty, gives 84.2 kg; Alfa Laval CB200-80M, 65.9 kg at 800 kW, gives 82.4 kg) | 84.2 | kg | Brazed | ^[4]^[32] |
| Plate thickness, Danfoss XGM032 | 0.4 | mm | Gasketed | ^[3] |
| Plate thickness, ACV 900 kW unit with 88 plates | 0.3 | mm | Brazed | ^[4] |
| Maximum working pressure, Danfoss traditional plate units | 35 | bar | Gasketed | ^[18] |
| Design pressure at 90 C, ACV 900 kW unit | 19 | bar | Brazed | ^[4] |
| Maximum working temperature, Danfoss traditional plate units | 180 | C | Gasketed | ^[18] |
| Water flow through the ACV 900 kW unit, 80 C to 60 C on the hot side | 10.8 | kg/s | Brazed | ^[4] |
| Pump power to overcome the unit's own 50 kPa pressure drop on one side of a 1 MW unit, pump efficiency 0.8 (calculated: Alfa Laval's 2,000 kW worked case of 287 m3/h halved, 5.1 m water head, divided by 367 and 0.8) | 2.5 | kW | Gasketed | ^[8] |

as of 2026-11-17

#### Variants

The variants whose make-up or footprint differs a lot, what defines each and its share of units

| Variant | Defining spec | Source |
|---|---|---|
| Gasketed | Stainless plates, each with a rubber gasket, held in a carbon steel frame; the pack can be opened for cleaning | ^[1]^[29] |
| Brazed | Stainless plates joined by copper brazing in a vacuum oven; no gaskets or frame | ^[29]^[4] |

as of 2026-11-17. Semi-welded and welded plate units also exist [7][29], but no source gives their material content per unit, so they are not separate variants here. No source gives variant shares of units.

#### Limits

The physical limits set by science and the engineering limits of today's design, with today's value

| Limit | Kind | Limit | Today | Unit | Source |
|---|---|---|---|---|---|
| Second law of thermodynamics: the cold liquid cannot leave hotter than the hot liquid enters, so the approach temperature stays above zero | Physical | 0 | approach as close as 1 | F | ^[6] |
| Pressure of gasketed plate units, set by the gaskets and their fixings (Danfoss gives up to 35 bar; a review gives up to 25 bar) | Engineering | 35 | up to 35 | bar | ^[18]^[29] |
| Temperature of gasketed plate units, set by the gasket rubber (Danfoss gives up to 180 C; a review gives a usual gasket range up to 150 C, or 200 C with special gaskets) | Engineering | 180 | up to 180 | C | ^[18]^[29] |
| Thinnest stamped plate, which sets how light the unit can be | Engineering | 0.3 | 0.4 (gasketed), 0.3 (brazed) | mm | ^[29] |

as of 2026-11-17

#### Science it relies on

The science principles it works by or is limited by
 Relies on

- [Heat conduction (Fourier's law)](https://www.materialinsights.org/science/heat_conduction/) Heat crosses each thin metal plate by conduction, so thin plates of conductive steel pass heat well.
- [Passivation and corrosion resistance](https://www.materialinsights.org/science/passivation/) Stainless steel plates resist corrosion through a thin protective surface film.
 Limited by

- [Second law of thermodynamics](https://www.materialinsights.org/science/second_law_thermodynamics/) Heat flows only from hot to cold, so the cold liquid can be warmed only towards the hot liquid's inlet temperature.

as of 2026-11-17

#### Sources

1. [Climate profile declaration: Alfa Laval gasketed plate heat exchangers T15, T10 and T6](https://assets.alfalaval.com/documents/p2d6c3f5a/alfa-laval-climate-profile-declaration-gasketed-plate-heat-exchangers-en.pdf) Alfa Laval, 2023
2. [Danfoss XGM032 data sheet](https://manualmachine.com/danfoss/xgm032/18797820-data-sheet) Danfoss (copy on manualmachine.com), 2019
3. [900kW Brazed plate heat exchanger kit (ACV PHEX spec sheet)](https://downloads.acv.com/ACV%20PHEX%20900kW%20Spec%20Sheet.pdf) ACV
4. [T5-BFG-75M, product page](https://shop.alfalaval.com/en-pl/tap-water-heating--c004/t5-bfg-75m--1289893-) Alfa Laval
5. [Gasketed plate heat exchangers: GPHE vs shell-and-tube](https://www.alfalaval.com/microsites/gphe/tools/gphe-vs-shell-and-tube/) Alfa Laval
6. [Gasketed plate-and-frame heat exchangers](https://www.alfalaval.com/products/heat-transfer/plate-heat-exchangers/gasketed-plate-and-frame-heat-exchangers/) Alfa Laval
7. [Save now, save later: what is the ideal pressure drop to specify for gasketed plate heat exchangers in HVAC applications](https://test03.alfalaval.com/globalassets/documents/industries/hvac/save-now-save-later_what-is-the-ideal-pressure-drop-to-specify-for-gasketed-plate-heat-exchangers-in-hvac-applications.pdf) Alfa Laval
8. [Traditional plate heat exchangers](https://www.danfoss.com/en-gb/products/heat-exchangers/dhs/gasketed-heat-exchangers/traditional-plate-heat-exchangers/) Danfoss
9. [Plate Heat Exchangers and Their Types of Construction (Encyclopedia entry adapted from Energies 16(13), 4976)](https://encyclopedia.pub/entry/46929) MDPI, Arsenyeva, Tovazhnyanskyy, Kapustenko, Klemes and Varbanov, 2023
10. [T8-BFG-63M, product page](https://shop.alfalaval.com/en-ua/radiator-heating--c003/t8-bfg-63m--1291255-) Alfa Laval
11. [CB200-80M, product page](https://shop.alfalaval.com/en-bg/floor-heating--c002/cb200-80m--1294423-) Alfa Laval

## Other sections

- [Summary](https://www.materialinsights.org/products/p_heat_exchanger/index.md)
- [Bill of materials](https://www.materialinsights.org/products/p_heat_exchanger/prod-bom/index.md)
- [Use case](https://www.materialinsights.org/products/p_heat_exchanger/prod-use/index.md)
- [Supply chain](https://www.materialinsights.org/products/p_heat_exchanger/prod-supply/index.md)
- [Footprint](https://www.materialinsights.org/products/p_heat_exchanger/prod-footprint/index.md)
- [Evolution](https://www.materialinsights.org/products/p_heat_exchanger/prod-evolution/index.md)
- [Interventions](https://www.materialinsights.org/products/p_heat_exchanger/prod-interventions/index.md)