# Transformers and power electronics: Levers

Source page: https://www.materialinsights.org/technologies/e_power_electronics/tech-levers/

Held back most by

Production

The physics is well understood and the materials are advancing: silicon carbide has a 3.3 eV band gap against 1.1 eV for silicon ^[11]. The squeeze is supply: think tank GTRI estimates India's transformer steel fell 30.6% short of demand in FY 2024 ^[12], and large power transformers now take up to four years to procure ^[13].

#### The six layers

Mathematics, science, engineering, production, economics, and resources and rules: what each gives, the idea in plain words, the limit (hard or soft) and how close today is, what could unlock it, and the maths behind it

Six layers make a technology possible, from the mathematics underneath to the resources and rules it needs at world scale. A **hard limit** comes from mathematics or nature and can only be sidestepped; a **soft limit** moves with effort, scale, money or policy.

1.  1 Mathematics Hard limit

Mathematics is the language of its physics

**What it gives.** The turns-ratio rule that sets voltage and current on each side of a transformer.

**The idea.** A physical law makes the transformer work and mathematics designs it, so the role is language. The ratio of the output to the input voltage equals the ratio of the number of turns on the two coils, and the power on both sides is the same in an ideal unit ^[9].

**The limit.** An ideal transformer neither makes nor loses power; real ones lose a little in the winding and the core.

**What could unlock it.** Switching converters build on the same bookkeeping: pulses are timed so the average voltage and current meet the load.

[HVDC HVDC links](https://www.materialinsights.org/technologies/e_hvdc/)

Show the maths Vs ÷ Vp = Ns ÷ Np

**Vs**
: the output (secondary) voltage, in volts

**Vp**
: the input (primary) voltage, in volts

**Ns**
: the number of turns on the secondary coil

**Np**
: the number of turns on the primary coil

**In plain words.** A transformer has two coils on one iron core. If the second coil has twice as many turns, it gives twice the voltage. The power stays the same, so twice the voltage means half the current. That is why long lines use high voltage: less current, less heat.

**Worked example.** The textbook's battery charger: 120 V in, 15.0 V out, 200 primary turns. Ns = 200 × 15 ÷ 120 = 25 turns (calculated) ^[9]. With 16.0 A on the output, the power is 15.0 × 16.0 = 240 W and the input current is 240 ÷ 120 = 2.00 A (calculated) ^[9].

2.  2 Science Hard limit

**What it gives.** Faraday's law of induction for the transformer, and the semiconductor band gap for the switch.

**The idea.** A changing magnetic flux through a coil induces a voltage in proportion to the number of turns and how fast the flux changes ^[10]. A power switch must also block high voltage when it is off: silicon carbide has a band gap of 3.3 eV against 1.1 eV for silicon, and a breakdown field about 7.3 times silicon's ^[11].

**The limit.** Energy conservation caps a transformer at 100%, and the breakdown field of the semiconductor sets how much voltage a given thickness of switch can block ^[11].

**What could unlock it.** Wide-gap materials such as silicon carbide move the limit: lower switching losses let devices run at higher frequencies, which allows smaller capacitors and inductors ^[11].

Show the maths emf = -N × ΔΦ ÷ Δt

**emf**
: the voltage induced in the coil, in volts

**N**
: the number of turns in the coil

**ΔΦ**
: the change in magnetic flux through the coil, in webers

**Δt**
: the time the change takes, in seconds

**In plain words.** A magnet moving past a coil of wire pushes a voltage along the wire. A faster change gives more voltage, and so do more turns. A steady field does nothing, which is why a transformer works only on alternating current.

**Worked example.** The textbook's coil: N = 200, flux change = A × B = 7.85 × 10^-3 m^2 × 1.25 T = 0.00981 Wb, in 0.0150 s. The size of emf = 200 × 0.00981 ÷ 0.0150 = 131 V (calculated) ^[10]. The minus sign only says the voltage opposes the change.

3.  3 Engineering Soft limit

**What it gives.** An iron core, windings, insulation and cooling for transformers, and fast switches with filters for converters.

**The idea.** Silicon carbide conducts heat three times as well as silicon, and its low switching losses allow higher frequencies ^[11]. India's IS 1180 sets five energy efficiency levels for distribution transformers, with maximum losses for existing levels cut in Amendment 4 ^[14].

**The limit.** Heat in the switch and in the windings and core, which the cooling and insulation must carry away.

**What could unlock it.** Better materials: silicon carbide's higher heat conduction and lower switching loss ^[11]; lower-loss levels in the transformer standard ^[14].

4.  4 Production Soft limit Binds most today

**What it gives.** Large quantities of core steel, copper, insulation and chips turned into finished units.

**The idea.** Think tank GTRI estimates India needed 400,000 tonnes of grain-oriented (CRGO) electrical steel in FY 2024, made 50,000, imported 239,200 and exported 11,400, leaving 277,800 tonnes for local use and a shortfall of 122,200 tonnes, or 30.6% of demand; PTI reported this in October 2024 ^[12]. These figures add up (calculated: 50,000 + 239,200 - 11,400 = 277,800), but they are a think tank's estimate, not an official count.

**The limit.** Core steel supply: imports were about 60% of demand (calculated: 239,200 ÷ 400,000), from countries like China, Japan, Russia and South Korea ^[12].

**What could unlock it.** More domestic steel capacity, or a different core material; the source names none.

5.  5 Economics Soft limit

**What it gives.** A price per unit that a utility or a developer will pay, with losses counted over decades.

**The idea.** The IEA says that, in real terms, power transformer prices have risen about 75% since 2019 and cable costs have nearly doubled ^[13]. The efficiency levels in IS 1180 let a buyer pay more upfront for lower losses ^[14].

**The limit.** Cost and delivery time: procurement takes up to four years for large power transformers ^[13].

**What could unlock it.** Standard designs and long-run framework orders are possible levers; the sources here do not give figures for them.

6.  6 Resources and rules Soft limit

**What it gives.** Standards, permits and delivery slots for the transformers every new plant and substation needs.

**The idea.** An IEA survey of industry leaders found that procurement now takes two to three years for cables and up to four years for large power transformers, twice as long as in 2021 ^[13]. India's IS 1180 amendment tightened the maximum losses allowed at each efficiency level, with a last implementation date of 30 March 2022 ^[14].

**The limit.** Grid build-out and renewable connections wait on equipment that takes years to deliver, and on imported steel ^[12]^[13].

**What could unlock it.** Loss standards are set by regulators ^[14]; delivery times depend on factory capacity and steel supply ^[12]^[13].

as of 2026-11-23

#### Sources

1. [Transformers (College Physics, section 23.7, undated)](https://openstax.org/books/college-physics/pages/23-7-transformers) OpenStax, 2026
2. [Electric Generators (College Physics, section 23.5, undated)](https://openstax.org/books/college-physics/pages/23-5-electric-generators) OpenStax, 2026
3. [Body of Knowledge for Silicon Carbide Power Electronics (undated)](https://nepp.nasa.gov/files/27644/NEPP-BOK-2016-GRC-Boomer-SiC-TN35760.pdf) NASA Electronic Parts and Packaging Program (Boomer, Lauenstein, Hammoud), 2026
4. [Transformer steel shortage could impact India's energy ambitions: GTRI](https://www.theweek.in/wire-updates/business/2024/10/28/dcm39-biz-steel-power-gtri.html) The Week (PTI, GTRI report), 2024
5. [Rising component prices and supply chain pressures are hindering the development of transmission grid infrastructure](https://www.iea.org/news/rising-component-prices-and-supply-chain-pressures-are-hindering-the-development-of-transmission-grid-infrastructure) IEA, 2025
6. [Guidelines for implementation of Amendment No. 4 to IS 1180 (Part 1): 2014](https://services.bis.gov.in/tmp/Guidelines_1180_A4_O2ga_2021-04-19.pdf) Bureau of Indian Standards, 2021

## Other sections

- [Summary](https://www.materialinsights.org/technologies/e_power_electronics/index.md)
- [Overview](https://www.materialinsights.org/technologies/e_power_electronics/overview/index.md)
- [Correlation](https://www.materialinsights.org/technologies/e_power_electronics/correlation/index.md)
- [Science and limits](https://www.materialinsights.org/technologies/e_power_electronics/science/index.md)
- [Value chain](https://www.materialinsights.org/technologies/e_power_electronics/valuechain/index.md)
- [Unit economics](https://www.materialinsights.org/technologies/e_power_electronics/economics/index.md)
- [Engineering methods](https://www.materialinsights.org/technologies/e_power_electronics/methods/index.md)
- [Equipment and suppliers](https://www.materialinsights.org/technologies/e_power_electronics/equipment/index.md)
- [Overview](https://www.materialinsights.org/technologies/e_power_electronics/tech-overview/index.md)
- [Science](https://www.materialinsights.org/technologies/e_power_electronics/tech-science/index.md)
- [Evolution](https://www.materialinsights.org/technologies/e_power_electronics/tech-evolution/index.md)
- [Materials](https://www.materialinsights.org/technologies/e_power_electronics/tech-materials/index.md)
- [Energy footprint](https://www.materialinsights.org/technologies/e_power_electronics/tech-energy-footprint/index.md)
- [Industries](https://www.materialinsights.org/technologies/e_power_electronics/tech-industries/index.md)
- [Relationships](https://www.materialinsights.org/technologies/e_power_electronics/links/index.md)