Building heat recovery: Engineering and integration
Small kit, low risk, but timing and space matter
What this tab covers Engineering and operating integration: how tightly it is coupled to the host process, how steady the waste stream is, and how hard it is to retrofit.These are small, mostly plug-in technologies with low coupling risk; the main engineering issues are installation quality and matching supply to demand in time.
Process interdependence (coupling risk)
FavourableFailure rarely stops the host. A drain-water unit simply stops preheating; a heat-pump water heater usually has a resistance element as backup; chiller heat recovery is a side loop that can be bypassed. The exception is ventilation: if an HRV or ERV fails in an airtight building, fresh-air supply is lost, so maintenance of fans and filters matters for health as well as energy.6
Load factor and intermittency
MixedSimple drain-water units only work when hot water is used and drained at the same time, as in a shower; a test house in Ontario recovered about 790 kWh a year. Chiller heat recovery works when cooling and hot-water demand coincide, which they do all day in hotels; the Mumbai hotel case saved about 80 litres of diesel a day. Ventilation recovery runs continuously but gains most in extreme seasons.28
Test-house drain-water recovery about 790 kWh/yr2 Hotel diesel saved about 80 L/day8Footprint and retrofit complexity
MixedDrain-water units need a vertical drain run below the shower, so they are easiest in new build. Heat-pump water heaters need about 700 cubic feet (about 20 m3) of surrounding air and lose efficiency in cupboards. HRV/ERV retrofit needs ducts, which is disruptive in existing homes. Kitchen demand control is a retrofit of sensors and fan drives: a 5,000 cfm hood cost about USD 43,000 installed.47
HPWH air space needed about 700 cubic feet4 Kitchen demand control, 5,000 cfm hood about USD 43,000 installed7Sources
- Evaluation of Residential Drain Water Heat Recovery Unit (study begun 2010) Sustainable Technologies Evaluation Program (Toronto and Region Conservation Authority), 2017
- Is a Heat Pump Water Heater Right for Your Home? ENERGY STAR (US EPA), 2023
- HVAC energy recovery ventilation (Energy Basics) US DOE Building Science Education
- Engineering and Construction Bulletin 2015-3: Demand control kitchen ventilation US Army Corps of Engineers (via WBDG), 2015
- Benefits of superheat recovery on chillers: case study for a hotel installation (Rane and Tandale), 21st IIR International Congress of Refrigeration International Institute of Refrigeration, 2003