Material Insights · Understanding the Material World

Transformer and power converter: Bill of materials

About these figures

Which unit, study and year the composition figures describe, and how they vary

Each variant is a different machine. Distribution: one 400 kVA Vijai Electricals transformer of 2,015 kg, 2026 declaration [2]. Power: one 40 MVA Matelec transformer of 73,000 kg, 2025 [3]. Inverter: one Sungrow SG350HX of 124.5 kg, 2023, with amounts calculated from mass shares [5]. Oil, paper, insulation and resin have no node and are not counted; the inverter's mixed plastics are linked without amounts. Grain-oriented steel, power semiconductor modules and drives are not yet product nodes.

as of 2026-11-13

Direct materials

The commodities and chemicals in one unit as bought, with amount, mass share, cost share and recycled content

Variant 1 Distribution transformer (400 kVA, oil-immersed)
MaterialRoleAmount in one unitShare of the unit's mass
St SteelStructural1102.5 kg54.7%
Magnetic steel 729 kg plus steel sheet 373.5 kg of the 2,015 kg Vijai unit (calculated sum) [2].
Al AluminiumFunctional405 kg20.1%
Low-voltage conductor of the Vijai unit [2]. The declaration lists no copper; 58.4 kg of 'other metal' is not counted.
Variant 2 Power transformer (40 MVA, oil-immersed)
MaterialRoleAmount in one unitShare of the unit's mass
St SteelStructural41,972.04 kg57.5%
Magnetic steel 24,424 kg plus steel 17,548.04 kg of the 73,000 kg Matelec unit (calculated sum) [3].
Cu CopperFunctional8280.15 kg11.3%
Copper conductor of the Matelec unit [3]. Oil (17,700 kg), wood and insulation (3,100 kg) have no node and are not counted; accessories (1,007 kg) are not counted either, though the end-of-life table treats them with the steel.
Variant 3 Inverter (352 kW solar string)
MaterialRoleAmount in one unitShare of the unit's mass
Al AluminiumStructural52.3 kg42%
42.0% of the 124.5 kg SG350HX (amount calculated: 0.420 x 124.5 kg) [5].
St SteelStructural21.4 kg17.2%
Stainless steel 5.2% plus other ferrous alloys 12.0% of the 124.5 kg unit (calculated: 0.172 x 124.5 kg) [5].
Cu CopperFunctional19.8 kg15.9%
15.9% of the 124.5 kg unit (amount calculated: 0.159 x 124.5 kg) [5].
PP PolypropyleneStructuralNot given –
Contains polypropylene (PP): the declaration gives PP, PC and PA together as 23.7% of the 124.5 kg unit, about 29.5 kg (calculated), with no split, so no amount is assigned to each polymer [5].
PC PolycarbonateStructuralNot given –
Contains polycarbonate (PC): the declaration gives PP, PC and PA together as 23.7% of the 124.5 kg unit, about 29.5 kg (calculated), with no split, so no amount is assigned to each polymer [5].
PA Nylon (PA6, PA66)StructuralNot given –
Contains polyamide (PA): the declaration gives PP, PC and PA together as 23.7% of the 124.5 kg unit, about 29.5 kg (calculated), with no split, so no amount is assigned to each polymer [5].

as of 2026-11-13

Cost breakdown

The share of the unit's cost in each component or stage

PartShare of costVariantYearSource
Copper23%Power transformer (large power transformer, US)2014[7]
Grain-oriented electrical steel (share of total manufacturing costs)25%Power transformer (large power transformer, US)2020[7]
Labour (share of total manufacturing costs)36%Power transformer (large power transformer, US)2020[7]
Copper and grain-oriented electrical steel together50%Power transformer (large power transformer, US)2022[7]

as of 2026-11-13. The DOE review takes copper's share from a 2014 DOE study and the steel and labour shares from a 2020 Department of Commerce survey of US makers, so the rows are not on one basis and do not add up [7].

How it is put together

The main steps from parts and materials to the finished unit

StepWhat happensSource
Cut and stack the coreGrain-oriented electrical steel sheets are cut and stacked into the core legs and yokes.–
Wind the coilsCopper or aluminium conductor is wound into coils and wrapped in paper and pressboard insulation.[3][4]
Assemble and dryCoils are fitted on the core and dried before they go in the tank.–
Tank and oilThe assembly goes into a steel tank filled with insulating oil; dry-type and resin units skip the oil.[3]
Test lossesLoad loss, no-load loss and impedance are measured; in India the amended rules, as summarised in secondary sources, require these tests under IS 2026 (Part 1):2011.[16]
Assemble an inverterPower switches, capacitors and a circuit board are fitted with a heat sink in an aluminium and steel enclosure.[5]

as of 2026-11-13

Technologies inside it

The technologies inside the product, with how much of each per unit

Embodies
  • PE Transformers and power electronics 1 unit The transformer or converter itself.
  • Tsr Transistor Inverter Inverters switch with power semiconductors such as transistors; the Sungrow declaration lists a circuit board and cables but gives no count of switches [5].

as of 2026-11-13

Sources

  1. Environmental Product Declaration: TR-400 kVA Transformer, models 110081 and 110169 (EPDITALY1233) Vijai Electricals Ltd (India), registered with EPDItaly, 2026, Tables 4, 7 and 10
  2. Power Transformer 40 MVA, FPT1847100 (EPDITALY0935) Matelec SAL, registered with EPDItaly, 2025, Tables 3, 4, 5 and 23
  3. Environmental Product Declaration Power Transformers 40/50 MVA (ONAN/ONAF), registration S-P-00053 ABB T&D S.p.A., 2003
  4. Environmental Product Declaration: String Power Inverters SG350HX, SG285HX, SG320HX, SG333HX (EPDITALY0458) Sungrow Power Supply Co., Ltd., registered with EPDItaly, 2023, Tables 4-1, 4-2, 5-1 and 7-1
  5. Electric Grid Supply Chain Review: Large Power Transformers and High Voltage Direct Current Systems US Department of Energy, 2022, Executive summary and sections 2.1.4 and 2.1.6
  6. Stricter Energy Efficiency Norms for Distribution Transformers (secondary summary of S.O. 5967(E), AI-assisted commentary) Advocate (Dr.) Abhishek Gandhi, advocategandhi.com, 2025