Transformer and power converter: Working
What it is
The product and the job it does, in a short paragraph
A transformer changes the voltage of alternating current; a power converter changes its form, from alternating to direct current or back, or sets its frequency. This node covers one transformer or converter under the trade heading for transformers, static converters and inductors. The functional unit is one transformer or converter; the reference sizes are a 400 kVA distribution transformer, a 40 MVA power transformer and a 352 kW solar string inverter [2][3][5].
as of 2026-11-13
How it works
How it does its job, step by step in plain words
A transformer has two windings on a steel core. Alternating current in the first winding makes a changing magnetic field in the core, which induces a voltage in the second; the ratio of turns sets the ratio of voltages. Losses are of two kinds: a no-load loss in the core whenever the unit is energised, and a load loss in the windings that grows with the square of the load [2][3]. Oil carries the heat to the tank. An inverter does a different job electronically: semiconductor switches open and close rapidly to build alternating current out of direct current, and at the declared 98.8% efficiency about 1.2% of the power is lost as heat [5].
as of 2026-11-13
Key specifications
The numbers that describe it, each with unit, variant, year and source
| Spec | Value | Unit | Variant | Year | Source |
|---|---|---|---|---|---|
| Rated power of the reference distribution transformer (20/0.42 kV) | 400 | kVA | Distribution transformer (400 kVA, oil-immersed) | 2026 | [2] |
| Mass of the reference distribution transformer | 2015 | kg | Distribution transformer (400 kVA, oil-immersed) | 2026 | [2] |
| Load loss | 3250 | W | Distribution transformer (400 kVA, oil-immersed) | 2026 | [2] |
| No-load loss | 387 | W | Distribution transformer (400 kVA, oil-immersed) | 2026 | [2] |
| Rated power of the reference power transformer (132/22.8 kV, ONAN) | 40,000 | kVA | Power transformer (40 MVA, oil-immersed) | 2025 | [3] |
| Mass of the reference power transformer | 73,000 | kg | Power transformer (40 MVA, oil-immersed) | 2025 | [3] |
| Load loss of the reference power transformer | 158.473 | kW | Power transformer (40 MVA, oil-immersed) | 2025 | [3] |
| AC power of the reference string inverter (SG350HX; 352 kVA at 30 degrees C) | 352 | kW | Inverter (352 kW solar string) | 2023 | [5] |
| Mass of the reference inverter | 124.5 | kg | Inverter (352 kW solar string) | 2023 | [5] |
| European efficiency, used as the efficiency in the declaration's use stage | 98.8 | % | Inverter (352 kW solar string) | 2023 | [5] |
as of 2026-11-13
Variants
The variants whose make-up or footprint differs a lot, what defines each and its share of units
| Variant | Defining spec | Year | Source |
|---|---|---|---|
| Distribution transformer | Steps medium voltage down to 420 V for homes and factories; 400 kVA and about 2 tonnes in the reference; aluminium low-voltage windings in the Indian reference unit | 2026 | No share of units found [2] |
| Power transformer | Connects grid levels at tens of MVA and above; 40 MVA and 73 tonnes in the reference, about 11% copper and 24% oil | 2025 | No share of units found [3] |
| Inverter | Semiconductor converter of direct to alternating current; 352 kW and 124.5 kg in the reference, mostly aluminium and plastic | 2023 | No share of units found; 589 GWac shipped in 2024 [10] |
as of 2026-11-13
Limits
The physical limits set by science and the engineering limits of today's design, with today's value
| Limit | Kind | Limit | Today | Unit | Source |
|---|---|---|---|---|---|
| Efficiency cannot reach 100% because winding resistance and core magnetisation never vanish (40 MVA unit at 70% load, calculated) | Physical | 100 | 99.66 | % | [3] |
| Efficiency of a string inverter (maximum of the SG350HX) | Engineering | 100 | 99.02 | % | [5] |
| Minimum peak efficiency index the EU requires of a 40,000 kVA liquid-immersed transformer from 1 July 2021 (a legal floor, not a physical limit) | Engineering | – | 99.724 | % | [13] |
| Time to build a large power transformer even when all materials are available | Engineering | – | 16 | weeks (12 to 16) | [7] |
as of 2026-11-13
Science it relies on
The science principles it works by or is limited by
Relies on- Electromagnetic induction A changing magnetic field in the core induces the voltage in the second winding.
- Band theory of solids The semiconductor switches of an inverter work because of the band structure of silicon.
- Ferromagnetism and magnetic domains Magnetising and demagnetising the steel core every cycle wastes energy even with no load.
- Ohm's law Current in the windings loses power as heat, which sets the load loss.
as of 2026-11-13
Sources
- Environmental Product Declaration: TR-400 kVA Transformer, models 110081 and 110169 (EPDITALY1233) Vijai Electricals Ltd (India), registered with EPDItaly, 2026, Tables 4, 7 and 10
- Power Transformer 40 MVA, FPT1847100 (EPDITALY0935) Matelec SAL, registered with EPDItaly, 2025, Tables 3, 4, 5 and 23
- Environmental Product Declaration: String Power Inverters SG350HX, SG285HX, SG320HX, SG333HX (EPDITALY0458) Sungrow Power Supply Co., Ltd., registered with EPDItaly, 2023, Tables 4-1, 4-2, 5-1 and 7-1
- Electric Grid Supply Chain Review: Large Power Transformers and High Voltage Direct Current Systems US Department of Energy, 2022, Executive summary and sections 2.1.4 and 2.1.6
- Global PV inverter shipments grew by 10% in 2024 to 589 GWac Wood Mackenzie, 2025
- Commission Regulation (EU) No 548/2014, Annex I (as adopted) legislation.gov.uk (EU legislation text), 2014