Underground, submarine and superconducting cables: Science
Principles
The science it rests on, with why each principle matters to it
Relies on- Ohm's law Current through the core is proportional to the voltage across it [9], so the core's resistance sets the heat a cable must shed and hence its size.
- Superconductivity Below a critical temperature some materials lose all electrical resistance [8], which lets a superconducting cable such as AmpaCity carry 2,300 A at only 10 kV [7].
- Maxwell's equations A cable's capacitance draws a charging current on AC, which limits a 380 kV AC cable to about 40 to 60 km without compensation [3].
as of 2026-11-11
Discoveries
The discoveries that made it possible: when, by whom and what was found
| Year | Who | What |
|---|---|---|
| 1827 | Georg Simon Ohm | Published the law linking current to the voltage across a conductor [9] |
| 1911 | Heike Kamerlingh Onnes | Found that the electrical resistance of mercury vanishes when it is cooled close to absolute zero [8] |
| 1986 | J. Georg Bednorz and K. Alex Müller | Reported superconductivity in a ceramic oxide at a higher temperature than any known before [10] |
as of 2026-11-11
Physical limits
The limits nature sets, today's best and how far there is still to go
| Limit | Value | Unit | Best today | Gap |
|---|---|---|---|---|
| Length of a 380 kV AC cable before its charging current needs compensation | 60 | km | DC links avoid the limit: Viking Link runs about 764 km [4] | AC cables beyond about 40 to 60 km need reactive power compensation [3] |
as of 2026-11-11. ENTSO-E gives the maximal length as about 40 to 60 km for 380 kV [3].
The science explained
The science behind it explained for a curious reader
Think of an AC cable as a very long, thin capacitor. The metal core is one plate, the earthed screen around it the other, and the insulation between them is thin compared with the air gap around an overhead wire. Each time the voltage swings, the cable has to be charged and discharged, so part of the current that flows does no useful work. In a short cable this does not matter. In a long one the charging current grows until it uses up much of the core's capacity, which is why a 380 kV AC cable reaches its practical limit at about 40 to 60 km [3]. Direct current charges the cable once and then flows steadily, so DC cables can run for hundreds of kilometres, as Viking Link does [4]. Superconducting cables attack the other loss, resistance, which vanishes when certain materials are cooled enough [8].
as of 2026-11-11
Sources
- HVAC cross-linked polyethylene (XLPE) Cables ENTSO-E Technopedia, 2025
- National Grid announces commercial operations of Viking Link National Grid, 2023
- Section of Superconducting cable Science Museum Group Collection
- Heike Kamerlingh Onnes: Facts Nobel Prize Outreach (NobelPrize.org)
- Georg Simon Ohm MacTutor History of Mathematics, University of St Andrews (J J O'Connor and E F Robertson), 2000
- Press release: The Nobel Prize in Physics 1987 Royal Swedish Academy of Sciences (NobelPrize.org), 1987