Variable speed drive: Interventions
Interventions
Changes that would cut emissions or material use, by lever and life stage, with effect per unit, readiness, adoption, evidence and who acts
| Lever | Life stage | Change | Effect per unit | Readiness | Adoption | Who acts | Source |
|---|---|---|---|---|---|---|---|
| Efficiency | Use | Fit a drive to a centrifugal pump or fan that now runs at full speed with a valve or damper | A 20% cut in speed can cut input power by about 50% [1]. ABB calculates average possible savings of 43% for 5,900 systems it prioritised after screening more than 10,500, a vendor figure [16]. | Deployed | About 25% of industrial motors have a drive (ABB, 2025) [16] | Plant and building operators | [1][16] |
| Efficiency | Use | Fit drives first on fans, where the EU saving is largest | EU savings potential by application: fans 29% of fan electricity (70.3 TWh a year), pumps 15% (36.0 TWh), compressors 4% (14.8 TWh) [15] | Deployed | EU motors with drives range from 1 to 54% by unit power (2020) [15] | Plant operators, building owners | [15] |
| Efficiency | Use | Extend minimum efficiency standards to drives, pumps, fans and compressors | Not quantified per unit in the sources opened; the EU has required IE2 drives since 1 July 2021 [19] | Deployed in the EU; under discussion elsewhere [18] | EU since 2021; India has adopted the IEC standard (IS 17123) [21] | Regulators | [18][19][21] |
| Design | Components design | Raise the drive's own efficiency | Each 0.1 percentage point on a 37 kW drive at 80% load and 6,000 hours a year saves about 180 kWh a year (calculated from 29.6 kW x 6,000 h x 0.1%) [3] | Deployed; 98.1% reached by a 90 kW drive [3] | Not found | Drive makers | [3] |
| Circularity | End of life | Collect drives and recycle the steel, aluminium and copper | Danfoss counts a credit of 230 kg CO2e for a 90 kW drive, about 70% of the 330 kg for making it (calculated) [3] | Deployed in life-cycle scenarios; rate not found | Not found | Makers, recyclers, owners | [3] |
as of 2026-11-17
Sources
- Adjustable Speed Drive Part-Load Efficiency, Motor Systems Tip Sheet #11 US Department of Energy, 2012
- Environmental Product Declaration iC7-Automation, Frame FA08 (EPD-IES-0025739:001) Danfoss A/S (The International EPD System), 2026
- Study on the energy-saving potential of electric motors with variable-speed drives in the European Union, final report Fraunhofer ICT (Schröder, Liebertseder and Doppelbauer) for CEMEP, 2023
- Efficient motors and drives could cut global energy use by up to 10% Drives & Controls (reporting the ABB white paper 'Achieving the COP28 UAE Consensus'), 2025
- Electric motor systems: why are they important? Energy Efficiency Policy Brief EMSA 9 IEA 4E Electric Motor Systems Annex (EMSA), 2025
- Ecodesign for motors and drives ABB
- IS 17123 (Part 9/Sec 1):2025, Adjustable speed electrical power drive systems, Part 9 Ecodesign for power drive systems, motor starters, Section 1 (identical to IEC 61800-9-1:2017) Bureau of Indian Standards, 2025