Variable speed drive: Working
What it is
The product and the job it does, in a short paragraph
A variable speed drive is power electronics that sits between the supply and an AC motor and sets how fast the motor turns, by changing the frequency and voltage it receives. The functional unit is one 37 kW low-voltage drive, the normal-duty rating of a common 400 V general-purpose model [10]. The scope is air-cooled drives for 380 to 480 V motors. Medium-voltage, DC and servo drives, soft starters and the motors themselves are left out.
as of 2026-11-17
How it works
How it does its job, step by step in plain words
The drive first turns the incoming alternating current into direct current with a diode rectifier [19]. Capacitors smooth that direct current. Fast transistor switches called IGBTs [22] then chop it into pulses, 4,000 times a second in the reference model [10]. By varying the width of the pulses, the drive builds a three-phase supply of the frequency and voltage it wants, and an induction motor turns at a speed that follows that frequency. A controller watches the motor current and holds the speed or torque asked for. On a pump or fan, power falls roughly with the cube of speed, so a 20% cut in speed can cut input power by about 50% [1]. A heat sink and fan carry away the drive's own losses.
as of 2026-11-17
Key specifications
The numbers that describe it, each with unit, variant, year and source
| Spec | Value | Unit | Variant | Year | Source |
|---|---|---|---|---|---|
| Rated power, normal duty | 37 | kW | Standard drive | 2024 | [10] |
| Rated power, heavy duty | 30 | kW | Standard drive | 2024 | [10] |
| Supply voltage, three phase, 50 to 60 Hz | 380 to 480 | V | Standard drive | 2024 | [10] |
| Net mass of the reference 37 kW drive | 28.2 | kg | Standard drive | 2024 | [10] |
| Mass per kW, calculated from 28.2 kg and 37 kW | 0.76 | kg/kW | Standard drive | 2024 | [10] |
| Switching frequency, nominal (adjustable 2 to 12 kHz) | 4 | kHz | Standard drive | 2024 | [10] |
| Efficiency used for the use stage of a 90 kW drive (converter losses only) | 98.1 | % | Standard drive | 2026 | [3] |
| Reference service life used in declarations | 10 to 15 | years | Standard drive | 2026 | [3][8][9] |
as of 2026-11-17
Variants
The variants whose make-up or footprint differs a lot, what defines each and its share of units
| Variant | Defining spec | Year | Source |
|---|---|---|---|
| Standard drive | Diode rectifier at the input and an IGBT inverter; the general-purpose drive this page describes | 2021 | The EU IE2 rule for drives covers this type [19]; no share of units found |
| Low-harmonic drive | Active input stage or filters keep current distortion (THD) below 10%, or the drive returns energy to the supply (regenerative); left out of the EU IE2 drive rule | 2021 | [19]; no share of units found |
as of 2026-11-17
Limits
The physical limits set by science and the engineering limits of today's design, with today's value
| Limit | Kind | Limit | Today | Unit | Source |
|---|---|---|---|---|---|
| Input power cut from a 20% speed cut, centrifugal pump or fan with no static lift | Physical | 50 | about 50 | % less input power | [1] |
| Constant-torque loads (cranes, conveyors, mixers, compressors): input power varies linearly with speed, so savings are smaller | Physical | – | linear | power against speed | [1] |
| Efficiency of a 20 hp PWM drive at 12.5% load (97% at full load; the figures come from one maker and no common test protocol exists) | Engineering | – | 86 | % | [1] |
| Pumping with on/off control where static lift is a large part of the head: drives are seldom cost-effective; they are worth considering where pumps run at least 2,000 hours a year and flow varies by 30% or more | Engineering | – | 2,000 hours and 30% flow variation | hours per year;% flow variation | [2] |
as of 2026-11-17
Science it relies on
The science principles it works by or is limited by
Relies on- Electromagnetic induction The drive's output frequency sets the speed of the rotating field that drags an induction motor's rotor round.
- Band theory of solids Silicon IGBT switches turn on and off because of how charge moves in doped semiconductors.
- Feedback control theory The controller compares measured current and speed with the set point and corrects the output.
- Heat conduction (Fourier's law) Switching and conduction losses must flow through the heat sink, which sets how much power a frame can carry.
as of 2026-11-17
Sources
- Adjustable Speed Drive Part-Load Efficiency, Motor Systems Tip Sheet #11 US Department of Energy, 2012
- Control Strategies for Centrifugal Pumps with Variable Flow Rate Requirements (Pumping Systems Tip Sheet #12, DOE/GO-102007-2230) US Department of Energy, Industrial Technologies Program, 2007
- Environmental Product Declaration iC7-Automation, Frame FA08 (EPD-IES-0025739:001) Danfoss A/S (The International EPD System), 2026
- ABB general machinery drives, ACS350, 7.5 kW: Environmental product declaration ABB, 2008
- Environmental Product Declaration NEPD-11916-11779: SINAMICS G220, frame size FSD1 Siemens AG (The Norwegian EPD Foundation), 2025
- Product data sheet: ATV630D37N4, Altivar Process ATV600, 37 kW normal duty, 380 to 480 V, IP21 Schneider Electric, 2024
- Ecodesign for motors and drives ABB
- Low voltage drives history ABB