Heat pump: Interventions
Try this in What if Switch on levers and see what changes in India by 2036.
Interventions
Changes that would cut emissions or material use, by lever and life stage, with effect per unit, readiness, adoption, evidence and who acts
| Lever | Life stage | Change | Effect per unit | Readiness | Adoption | Who acts | Source |
|---|---|---|---|---|---|---|---|
| Substitute | Use | Replace a gas boiler with an air-to-water heat pump | Fraunhofer ISE found a calculated CO2 cut of 68% against gas heating in 77 monitored systems, and 64% on 2024 grid data; the IEA says at least 20% in all major markets with today's refrigerants | Deployed | 2.9 million heat pumps sold in 21 European countries in 2025 | Households, installers, governments | [7][9][13] |
| Efficiency | Use | Run at a lower flow temperature (bigger radiators, floor heating, better insulation) | An 8.5 kW unit has a SCOP of 4.84 at 35 °C and 3.48 at 55 °C, so over a season heating at 55 °C needs about 39% more electricity for the same heat (calculated: 4.84 / 3.48 = 1.39) | Deployed | Not found | Installers, owners | [5] |
| Design | Components design | Use propane (R-290) instead of R-32 or R-410A | GWP 0.02 against 675 and 2,088; a 0.9 kg propane charge is 0.018 kg CO2e if released, against 1,485 kg CO2e for the 2.2 kg R-32 charge of the 8.5 kW unit (calculated) | Deployed | R-290 in Vaillant's aroTHERM plus; from 1 January 2027 the EU bars F-gases with a GWP of 150 or more in self-contained heat pumps up to 12 kW, except where safety rules require them | Makers, regulators | [15][1][5][14] |
| Change route | Use | Run on cleaner electricity | The use stage is 92% of the life-cycle emissions of the 7 kW Vaillant system (17,701 of 19,209 kg CO2e, calculated) and 97.6% of the 8.5 kW Mitsubishi system (calculated) | Deployed | Depends on each grid | Utilities, governments | [1][5] |
| Efficiency | Use | Choose a ground source unit where land and budget allow | Field SPF 4.3 against 3.4 for air-to-water units, about 21% less electricity for the same heat (calculated: 1 minus 3.4 / 4.3), but in the one inventory found, two 90 m boreholes add 300.6 kg of materials to a dual-source unit (calculated) | Deployed | 16 of 77 monitored German units were ground source | Owners, installers | [7][6] |
| Circularity | End of life | Recover the refrigerant and recycle the metals | EPD scenarios assume 65% of the refrigerant recovered and 70% of metals recycled (Mitsubishi), or 87% to 95% metal recycling (Vaillant); measured rates were not found | Scenario assumptions; deployed practice not measured in the sources opened | Not found | Installers, recyclers, makers | [5][1] |
as of 2026-11-13
Sources
- Environmental Product Declaration as per ISO 14025 and EN 15804: aroTHERM plus 7 kW & uniTOWER plus (EPD-Kiwa-EE-000387, issued 13.03.2024) Vaillant GmbH, Kiwa-Ecobility Experts, 2024, Tables 1, 2, 8, 12, 14
- Environmental Product Declaration to EN 15804 (BRE Global programme): Mitsubishi Electric air source heat pumps of 5, 6, 8.5, 11.2 and 14 kW with EHPT20X-MHEDW 200 L packaged cylinder (undated; manufacturing data 1 April 2021 to 31 March 2022) Mitsubishi Electric, BRE Global, Technical information, Main Product Contents, LCA results for PUZ-WM85VAA, scenarios
- Data on the environmental performance analysis of a dual-source heat pump system Data in Brief 31, article 105919 (Marinelli, Butturi, Lolli, Rimini, Gamberini), 2020, Tables 1 to 3
- Fraunhofer ISE research project completed: heat pumps provide climate-friendly heating in existing buildings Fraunhofer ISE, 2025
- The Future of Heat Pumps: Executive summary IEA, 2022
- Market data European Heat Pump Association (EHPA)
- Air conditioning - Climate-friendly alternatives to F-gases European Commission, Climate Action
- Global Warming Potentials (GWP) of selected compounds and their mixtures (AR4, AR5 and Regulation (EU) 2024/573), March 2026 Umweltbundesamt (German Environment Agency), 2026, Tables 1, 3, 4