Heat and thermodynamics: engines, heat pumps and their limits: Refrigerators, air conditioners and heat pumps: moving heat uphill
All courses / Understanding Engineering / Module 6: Heat and thermodynamics: engines, heat pumps and their limits Part 4 of 5Refrigerators, air conditioners and heat pumps: moving heat uphill
A heat engine lets heat fall from hot to cold and takes work from the fall. Run it backwards and you get a machine that spends work to lift heat from cold to hot: a refrigerator, an air conditioner or a heat pump. They are the same machine in three jobs. This part shows how the loop works, why it can deliver three or four units of heat for each unit of electricity, and what that means for a bedroom in May.
4.1 A refrigerator is a heat engine run backwards: a compressor lifts heat from a cold space to a warm one
A split air conditioner hides a closed loop of refrigerant that passes through four parts. Start at the compressor in the outdoor unit. It takes in cool vapour and squeezes it to high pressure, which also makes it hot. In the condenser coil beside it, the vapour condenses at 45 to 55 °C, some 10 to 15 K above the outdoor air, so heat flows out of it into that air and it turns to liquid. The warm liquid then passes an expansion valve or a thin capillary tube, where its pressure falls sharply; part of it flashes to vapour and the rest is chilled to about 5 to 10 °C. Indoors, in the evaporator, this cold liquid boils, taking its latent heat from room air that a fan blows across the fins, and the vapour returns to the compressor. A refrigerator runs the same loop with an evaporator near minus 20 °C. See the nodes Refrigerator and Air conditioner.
The trick is pressure. By raising the pressure, the compressor raises the temperature at which the fluid condenses, so the same fluid can absorb heat at a cold temperature and release it at a warm one. Cooling is quoted in watts of heat removed or in tonnes of refrigeration, where one tonne is 3.5 kW.
The first law fixes the audit: heat released outside = heat taken from inside + electrical work done on the refrigerant. So any such machine sitting wholly inside a closed space warms that space overall. A deep freezer running in a small, shut storeroom heats the room by the full power it draws, even while it chills its contents.
The trade-off lies in the temperatures. A lower evaporating temperature or a higher condensing temperature means more lift, more work and a lower efficiency. A dirty condenser coil in an Indian summer is a measurable energy cost.
liquid boils at about 10 °C and absorbs the room's heat
2 Compressorvapour is squeezed to a high pressure and hot temperature; this is where the work goes in
3 Condenser (outdoors)vapour at about 50 °C gives up heat to the outside air and becomes liquid
4 Expansion valvepressure drops and the liquid is cooled back to 10 °C or less
Outputs Heat to the outdoorsabout 2.4 kW (2.0 + 0.4)Round numbers for an inverter unit at a seasonal COP near 5; the 2 kW load is assumed. The audit is exact: heat out = heat in + work.
Source: Bloomfield, How Things Work (Wiley, 2015), ch. 8, 'Thermodynamics', section 8.1 ('Air Conditioners': evaporator, compressor and condenser)- Bloomfield, How Things Work (Wiley, 2015) · ch. 8, 'Thermodynamics', section 8.1 ('Air Conditioners')
4.2 The coefficient of performance can exceed one because the machine moves heat instead of making it
The measure of a cooling machine is the coefficient of performance, COP: heat removed divided by work put in. A resistance heater gives at best one joule of heat per joule of electricity. A refrigerator is different, because it does not make the heat it delivers. It lifts it, and lifting a joule a short way costs only a fraction of a joule. So the COP is commonly 3 to 5, and the electrical meter reads only one-third to one-fifth of the heat moved.
The second law again sets the ceiling. For an ideal machine the cooling COP is Tc / (Th - Tc), the cold temperature over the temperature lift, with both in kelvin. It is large when the lift is small. A room at 297 K (24 °C) against 308 K outside, a lift of 11 K, would allow a COP of 27. But the refrigerant must be colder than the room and hotter than the outside to let heat flow, so the real lift is more like 40 K. That drops the ideal COP to about 7, and the real machine reaches 4 to 5, or 60 to 70 per cent of ideal. In India, efficiency is labelled as ISEER, the ratio of cooling delivered to electricity used over a standard year of Indian weather. The Bureau of Energy Efficiency's star table of July 2022 asked at least 5.0 for five stars and 3.3 for one. A May 2026 Berkeley analysis treats 5.3 as today's 5-star level and proposes minimum standards of 5.3 by 2030 and 6.7 by 2033, beyond the 4.3 minimum the Bureau plans for 2028.
The table works out a bedroom. The trade-off is plain: a higher star rating costs more to buy, for bigger heat exchangers and a variable-speed compressor, and repays the extra in a few summers.
| Step | Working | Result |
|---|---|---|
| Average heat load on a 12 m2 top-floor bedroom at night (assumed) | two sleepers 160 W + devices 100 W + roof and walls giving back the day's heat 1,400 W + warm air leaking in 340 W | about 2.0 kW |
| Electric draw, 5-star inverter, ISEER 5.3 taken as COP | 2.0 / 5.3 | 0.38 kW |
| Energy for 8 hours | 0.38 x 8 | 3.0 kWh |
| Cost at an assumed Rs 8 per kWh | 3.0 x 8 | about Rs 24 a night |
| Older fixed-speed unit, COP 3.0 | 2.0 / 3.0 = 0.67 kW; x 8 h = 5.3 kWh | about Rs 43 a night |
| Difference over 150 hot nights | (43 - 24) x 150 | about Rs 2,800 a year |
Results calculated; the load items and tariff are assumed round values. Check: monitored 1.5 tonne inverter units commonly average 0.5 to 1 kW when running in Indian summers, because they run at full output for the hottest hours, so the night figures here are the lower end.
Source: Bloomfield, How Things Work (Wiley, 2015), ch. 8, 'Thermodynamics', section 8.1 ('Air Conditioners': ideal heat pump relationships)- Bloomfield, How Things Work (Wiley, 2015) · ch. 8, 'Thermodynamics', section 8.1 ('Air Conditioners')
- Beating the Heat: How Air Conditioner Efficiency Standards Help India Avert Power Shortages and Cut Consumer Bills (Abhyankar, Domínguez Bennett and Phadke, India Energy and Climate Center, University of California, Berkeley, May 2026) · ISEER 5.3 as the current 5-star level; BEE's planned 4.3 minimum for 2028 and proposed minimums of 5.3 in 2030 and 6.7 in 2033; air conditioners up to 60 to 70 GW, about 25 per cent of peak demand; https://live-iecc-gspp.pantheon.berkeley.edu/resources/reports/beating-the-heat-ac-efficiency-standards/
- Press Information Bureau, Ministry of Power, star labelling programme and split air conditioners (10 May 2023) · split AC ISEER thresholds: 1-star 3.3 and 5-star 5.0 for the table in force from July 2022; https://www.pib.gov.in/PressReleaseIframePage.aspx?PRID=1923031®=48&lang=2
4.3 A heat pump is the same loop aimed at the room, and it warms water for a third of the electricity a geyser needs
If you want the heat rather than the cold, point the loop the other way. A heat pump takes heat from a cool source, such as outdoor air, the ground or a flow of waste water, and delivers a larger amount at a warmer temperature, where it is wanted. Its heating COP is the heat delivered divided by the work, equal to the cooling COP plus one, because the heat delivered is the heat taken in plus the work. The ideal value is Th / (Th - Tc). See the node Heat pump: it is a refrigerator used for its hot side.
India's demand for heating is mostly hot water rather than rooms. A geyser turns each unit of electricity into one unit of heat. A heat pump water heater working between air at about 20 °C and a tank at 60 °C has an ideal COP of 333/40 = 8.3. Real units reach about 3, after compressor losses, temperature gaps in the exchangers and fan power. The table works through a household example. Industry drying tea, textiles or milk powder at 60 to 120 °C can use the same logic.
The limits are those of the second law. The higher the temperature wanted, the lower the COP, and a heat pump that tries to deliver 150 °C from a 30 °C source will have a COP near two even at its best. An air-source heater in Leh or Srinagar meets the worst case: in January the air it draws on is well below freezing just when hot water is most wanted, so its COP sags towards two or three. And a heat pump costs several times as much as a resistance geyser, so it pays only where it runs for many hours.
| Option | Working | Electricity per day |
|---|---|---|
| Heat needed, 25 °C to 55 °C | 100 kg x 4.19 kJ/kg K x 30 K = 12.6 MJ | 3.5 kWh of heat |
| Electric geyser, efficiency close to 1 | 3.5 / 1 | 3.5 kWh |
| Heat pump water heater, COP 3 | 3.5 / 3 | 1.2 kWh |
| Saving per day at Rs 8 per kWh | (3.5 - 1.2) x 8 | about Rs 18 |
| Saving in 300 days | 18 x 300 | about Rs 5,500 a year |
| Solar heater, clear day | see estimate 2 | close to 0 kWh |
Results calculated; tariff, COP and the Rs 40,000 price gap are assumed. Standing losses from the tank are ignored in all options. Simple payback is a little over seven years.
Source: Bloomfield, How Things Work (Wiley, 2015), ch. 8, 'Thermodynamics', section 8.1 ('Air Conditioners': heat pumps)- Bloomfield, How Things Work (Wiley, 2015) · ch. 8, 'Thermodynamics', section 8.1 ('Air Conditioners')
- Feynman, Leighton and Sands, The Feynman Lectures on Physics, vol. I (Caltech online edition) · further reading: ch. 45, 'Illustrations of Thermodynamics', https://www.feynmanlectures.caltech.edu/I_45.html
See it in the table
H₂O WaterTea TeaEl ElectricityCheck your understanding
A window air conditioner removes 3.0 kW of heat from a room using 1.0 kW of electricity. How much heat does it discharge outdoors?
Heat out = heat in + work = 3.0 + 1.0 = 4.0 kW. The COP of 3 means three units of heat were moved per unit of work, and the work also ends up as heat outside.Why does the ideal cooling COP get larger when the temperature lift gets smaller?
Lifting heat through a short temperature step costs little work. The formula Tc / (Th - Tc) shows it: with Th - Tc in the denominator, a smaller lift gives a larger ideal COP, and that is why a high-ISEER unit tries to keep the gaps small.A heat pump water heater with COP 3 versus an electric geyser, for the same hot water, uses about
The geyser makes each kWh of electricity into 1 kWh of heat. The heat pump moves two more units of heat from the surroundings for each unit of electricity, so it needs a third of the electricity for the same heat.