Heat exchanger: Working
What it is
The product and the job it does, in a short paragraph
A plate heat exchanger passes heat from one liquid to another through thin metal plates, keeping the two liquids apart. The functional unit is one plate heat exchanger of 1 MW duty. The scope is heat-exchange units of HS 8419.50 built from stacked plates, gasketed or brazed. Shell and tube, air-cooled and welded block units, economisers and recuperators are left out. Masses here are scaled from maker units of 0.5 to about 1.2 MW [5][4][31][32].
as of 2026-11-17
How it works
How it does its job, step by step in plain words
A pack of corrugated plates is stacked so that the hot and cold liquids run in alternate channels [1]. The corrugations create strong turbulence over the whole plate, which raises heat transfer and reduces fouling [6]. Heat crosses each plate by conduction. Counter-current flow gives the most efficient performance, and close temperature approaches are possible [7][6]. In a gasketed unit, rubber gaskets seal the channels and the pack is held in a frame. In a brazed unit the plates are joined with copper in a vacuum oven, so there are no gaskets [29]. External pumps push the liquids through. A higher pressure drop needs fewer plates and costs less to buy, but costs more to pump [8].
as of 2026-11-17
Key specifications
The numbers that describe it, each with unit, variant, year and source
| Spec | Value | Unit | Variant | Source |
|---|---|---|---|---|
| Mass of a 1 MW unit, gasketed (calculated by scaling linearly with duty: Alfa Laval T5-BFG-75M, 100.9 kg at 500 kW, gives 201.8 kg; Alfa Laval T8-BFG-63M, 266 kg at 1,000 Mcal/h or about 1,163 kW, gives 228.7 kg) | 201.8 | kg | Gasketed | [5][31] |
| Mass of a 1 MW unit, brazed (calculated by scaling linearly with duty: ACV 900 kW unit, 75.8 kg empty, gives 84.2 kg; Alfa Laval CB200-80M, 65.9 kg at 800 kW, gives 82.4 kg) | 84.2 | kg | Brazed | [4][32] |
| Plate thickness, Danfoss XGM032 | 0.4 | mm | Gasketed | [3] |
| Plate thickness, ACV 900 kW unit with 88 plates | 0.3 | mm | Brazed | [4] |
| Maximum working pressure, Danfoss traditional plate units | 35 | bar | Gasketed | [18] |
| Design pressure at 90 C, ACV 900 kW unit | 19 | bar | Brazed | [4] |
| Maximum working temperature, Danfoss traditional plate units | 180 | C | Gasketed | [18] |
| Water flow through the ACV 900 kW unit, 80 C to 60 C on the hot side | 10.8 | kg/s | Brazed | [4] |
| Pump power to overcome the unit's own 50 kPa pressure drop on one side of a 1 MW unit, pump efficiency 0.8 (calculated: Alfa Laval's 2,000 kW worked case of 287 m3/h halved, 5.1 m water head, divided by 367 and 0.8) | 2.5 | kW | Gasketed | [8] |
as of 2026-11-17
Variants
The variants whose make-up or footprint differs a lot, what defines each and its share of units
| Variant | Defining spec | Source |
|---|---|---|
| Gasketed | Stainless plates, each with a rubber gasket, held in a carbon steel frame; the pack can be opened for cleaning | [1][29] |
| Brazed | Stainless plates joined by copper brazing in a vacuum oven; no gaskets or frame | [29][4] |
as of 2026-11-17. Semi-welded and welded plate units also exist [7][29], but no source gives their material content per unit, so they are not separate variants here. No source gives variant shares of units.
Limits
The physical limits set by science and the engineering limits of today's design, with today's value
| Limit | Kind | Limit | Today | Unit | Source |
|---|---|---|---|---|---|
| Second law of thermodynamics: the cold liquid cannot leave hotter than the hot liquid enters, so the approach temperature stays above zero | Physical | 0 | approach as close as 1 | F | [6] |
| Pressure of gasketed plate units, set by the gaskets and their fixings (Danfoss gives up to 35 bar; a review gives up to 25 bar) | Engineering | 35 | up to 35 | bar | [18][29] |
| Temperature of gasketed plate units, set by the gasket rubber (Danfoss gives up to 180 C; a review gives a usual gasket range up to 150 C, or 200 C with special gaskets) | Engineering | 180 | up to 180 | C | [18][29] |
| Thinnest stamped plate, which sets how light the unit can be | Engineering | 0.3 | 0.4 (gasketed), 0.3 (brazed) | mm | [29] |
as of 2026-11-17
Science it relies on
The science principles it works by or is limited by
Relies on- Heat conduction (Fourier's law) Heat crosses each thin metal plate by conduction, so thin plates of conductive steel pass heat well.
- Passivation and corrosion resistance Stainless steel plates resist corrosion through a thin protective surface film.
- Second law of thermodynamics Heat flows only from hot to cold, so the cold liquid can be warmed only towards the hot liquid's inlet temperature.
as of 2026-11-17
Sources
- Climate profile declaration: Alfa Laval gasketed plate heat exchangers T15, T10 and T6 Alfa Laval, 2023
- Danfoss XGM032 data sheet Danfoss (copy on manualmachine.com), 2019
- 900kW Brazed plate heat exchanger kit (ACV PHEX spec sheet) ACV
- T5-BFG-75M, product page Alfa Laval
- Gasketed plate heat exchangers: GPHE vs shell-and-tube Alfa Laval
- Gasketed plate-and-frame heat exchangers Alfa Laval
- Save now, save later: what is the ideal pressure drop to specify for gasketed plate heat exchangers in HVAC applications Alfa Laval
- Traditional plate heat exchangers Danfoss
- Plate Heat Exchangers and Their Types of Construction (Encyclopedia entry adapted from Energies 16(13), 4976) MDPI, Arsenyeva, Tovazhnyanskyy, Kapustenko, Klemes and Varbanov, 2023
- T8-BFG-63M, product page Alfa Laval
- CB200-80M, product page Alfa Laval